Emergency Exit Sign System (EXIT SIGNS)
Location: Perris, California
Service Date: 04/18/2026
Service Type: Corrective Maintenance
Corrective maintenance was performed on the exit sign system, including prior diagnostics, replacement of defective batteries, and operational verification in compliance with applicable codes.
Total units inspected: 6 Exit Signs
Non-operational units: 4 (due to breaker in OFF position – condition corrected)
Units with backup failure: 2 (defective batteries)
4.1 Battery Replacement
Replacement of internal batteries in defective units:
- 1 rechargeable battery 4.8V (Ni-Cd)
- 1 rechargeable battery 1.2V (Ni-Cd)
Technical criteria applied:
- Voltage compatibility
- Equivalent battery type
- Compatible original connectors
- Opening of exit sign fixture
- Disconnection of defective battery
- Installation of new battery
- Polarity verification
- Reconnection and closure of unit
6.1 Normal Operation Test
- Continuous illumination verified
- LED indicators operational
6.2 Emergency Test (Power Loss Simulation)
- Proper activation in battery mode
- Stable illumination during test
Operational units: 6 / 6
System restored: 100% functional
The system complies with the following standards:
- NEC 2020 (NFPA 70)
- NFPA 101 (Life Safety Code)
- OSHA
Final status: COMPLIANT
Perform periodic testing:
- Monthly: functional test (30 seconds)
- Annual: full discharge test (90 minutes)
Record battery replacement date
Keep circuit #42 permanently energized
Label breaker as: "EXIT SIGNS – DO NOT TURN OFF"
The repair of the exit sign system was successfully completed through replacement of defective batteries, restoring continuous operation and code compliance.
System operational and compliant with current codes.